Cable Gands for Mining E1FW and E1FW/F
Application
Single wire armoured cable types.
Dry Indoors
Applicable Standard
BS 6121.
Fitting Instructions
1. Seperate gland into its two component parts and pass item 2 over the cable.
2. Strip back outer sheath and armour to suit equipment geometry.
3. Expose armouring by further stripping outer sheath for a length equivalent to the item 1 knurl plus 5mm.
4. Secure Item 1 into the equipment.
5. Pass cable through item 1, equally spacing armoured wires on knurled cone.
6. Lock armouring by tightening item 2 onto item 1.
Note: Item 1 and Item 2 should not lock face to face.
|
Gland Size |
Thread Entry |
Entry seal Closure |
Bottom Seal |
Length |
Envelope |
Armour Wire |
Shroud |
||
|
20S |
20 |
3/4" |
15 |
11.7 - 5.9 |
16.0 - 11.2 |
70.0 |
30.5 |
0.9 / 1.25 |
161 |
|
20 |
20 |
3/4" |
15 |
14.0 - 6.4 |
21.0 - 13.2 |
68.0 |
33.5 |
0.9 / 1.25 |
162 |
|
25S |
25 |
1" |
15 |
20.0 - 10.0 |
24.0 - 15.5 |
78.0 |
40.0 |
1.25 / 1.60 |
163 |
|
25 |
25 |
1" |
15 |
20.0 - 10.0 |
27.5 - 22.5 |
78.0 |
40.0 |
1.25 / 1.60 |
163 |
|
32 |
32 |
1 1/4" |
15 |
26.3 - 19.0 |
34.0 - 26.4 |
78.0 |
51.5 |
1.60 / 2.00 |
164 |
|
40 |
40 |
1 1/2" |
15 |
32.2 - 25.0 |
40.5 - 31.5 |
62.0 |
61.5 |
1.60 / 2.00 |
165 |
|
For Spigot and flange bolting See Adaptor Flange Data Sheet. |
|||||||||