Cable Gands for Mining E1FW and E1FW/F

 

 

 

 

 

 

 

 




Application 

Single wire armoured cable types.
Dry Indoors

Applicable Standard

BS 6121.

Fitting Instructions

1. Seperate gland into its two component parts and pass item 2 over the cable.
2. Strip back outer sheath and armour to suit equipment geometry.
3. Expose armouring by further stripping outer sheath for a length equivalent to the item 1 knurl plus 5mm.
4. Secure Item 1 into the equipment.
5. Pass cable through item 1, equally spacing armoured wires on knurled cone.
6. Lock armouring by tightening item 2 onto item 1.
Note: Item 1 and Item 2 should not lock face to face.

 Gland Size

 Thread Entry
Dia. 'C' Length
Metric Imp 'D' Min.

 Entry seal Closure
Range
Max.'A'Min.

 Bottom Seal
Closure
Range Max 'B' Min

 Length
'E'
Max.

 Envelope
Dia.
'F'

Armour Wire
Dia. 

 Shroud
Ref.

 20S

20

 3/4"

15

11.7 - 5.9 

 16.0 - 11.2

70.0

30.5

0.9 / 1.25 

161

 20

 20

 3/4"

 15

14.0 - 6.4 

21.0 - 13.2 

 68.0

 33.5

0.9 / 1.25 

162

 25S

 25

 1"

15

20.0 - 10.0 

 24.0 - 15.5

78.0

40.0

1.25 / 1.60 

163

 25

 25

 1"

 15

 20.0 - 10.0

27.5 - 22.5 

78.0

40.0

1.25 / 1.60 

163

 32

 32

 1 1/4"

 15

 26.3 - 19.0

 34.0 - 26.4

78.0

51.5

 1.60 / 2.00

164

 40

 40

 1 1/2"

15

32.2 - 25.0 

40.5 - 31.5 

62.0

61.5

1.60 / 2.00 

165

For Spigot and flange bolting See Adaptor Flange Data Sheet.
DETAILS OF LARGER SIZES (UP TO 75mm) - ON REQUEST
All Dimensions in millimetres unless shown otherwise.